Thermal Design of a High-Heat-Flux Condensation System

43 kWheat duty, steam at 60 °C and 0.0106 MPa
40 tubescopper, Ø12.7 mm × 1.51 m, 4 passes
2.40 m²heat transfer area, U ≈ 2050 W/(m²·K)
0.31 bartube-side pressure drop (limit 2 bar)
Q = U · A · ΔTlmαN = α1 · N−1/6
Problem
Design a condenser that fully condenses water vapour entering at 0.010627 MPa and 60 °C, rejecting 43 kW to cooling water that enters at 33 °C. At this low pressure the steam is superheated by 13 K above its 47 °C saturation temperature, so the unit has to desuperheat and condense it, keep the water velocity and pressure drop within limits, and stay compact.
Approach
- Design conditions: saturation temperature 47 °C; cooling water leaving at 42 °C (5 K approach); fluid properties from REFPROP.
- Temperature difference: LMTD of 8.74 K, with correction factor F = 1 for isothermal condensation.
- Tubes: copper for its conductivity, ½” tubes (12.7 × 1.245 mm), water velocity within 1.2–1.8 m/s. Tube count and length compared for 1 to 8 passes; 4 passes balance length, tube count and pressure drop.
- Shell sizing: bundle diameter found iteratively with the incomplete-packing correction factor φ, extrapolated below the chart’s 200 mm range, giving a 149 mm bundle and a 173.7 mm shell.
- Heat transfer: Dittus–Boelter on the tube side (Re ≈ 20,800); Nusselt film condensation on the shell side with the N−1/6 correction for condensate falling onto lower tubes; overall coefficient including fouling and wall resistance, iterated twice on the wall temperature.
- Mechanical checks: baffle spacing and maximum unsupported tube length (939 mm) verified.
- Pressure drops: Darcy–Weisbach plus inlet and outlet losses in the tubes; Kern’s method on the shell side for vapour-only and liquid-only flow, plus a Lockhart–Martinelli two-phase estimate.
The whole calculation is reproduced by a Python script in the repository, which prints every result and generates the design plots.
Results
- Final design: 40 copper tubes of 1.51 m in 4 passes on a 30° triangular pitch of 17.78 mm, inside a 173.7 mm shell with 4 baffles.
- Heat transfer: 2.40 m² of area with an overall coefficient of about 2050 W/(m²·K), down from 4.92 m² at the first-guess coefficient of 1000 W/(m²·K).
- Flow rates: 1.14 kg/s of cooling water and 0.018 kg/s of steam.
- Tube side: 0.31 bar pressure drop, well below the 2 bar limit.
- Shell side: about 4.4 kPa in the conservative vapour-only case. This is close to the limit for vacuum operation, so a larger shell or double-segmental baffles would be the next step to gain margin.