Design and Sizing of an HVAC System for a Residential Building

2.51 kWpeak heating load at −5 °C
3.28 kWpeak cooling load (Carrier method)
174 LDHW storage, 5.08 kW coil
5,743 kWhheating demand per year (55 kWh/m²)
Ptot = (HT + HV) · (ti − te)
Problem
Design the complete heating, cooling and hot-water system for a single-storey apartment in Padova (climatic zone E): size every component from the room loads up to the heat pump, and choose equipment that is neither undersized on the coldest day nor oversized for the rest of the year.
Approach
- Peak heating load: transmission and ventilation losses room by room at −5 °C outdoor and 20 °C indoor, cross-checked against a single-zone model of the whole dwelling (identical total).
- Seasonal demand: degree-days method (HDD = 2383).
- Domestic hot water: indirect storage tank with an immersed coil, sized from a two-phase energy balance (pre-heating and supply), plus annual demand to UNI/TS 11300-2. I also wrote a Python tool that solves this balance interactively.
- Cooling load: Carrier method over 24 hours, combining opaque walls, windows, solar gains, internal gains and infiltration, with storage and attenuation factors for the heavy masonry.
- Radiant floor (EN 1264): pipe pitch chosen per room at a fixed supply temperature (35 °C heating, 15 °C cooling), with mass flows, circuit lengths and pressure drops.
- Heat pump: two sizing strategies compared, additive (heating + DHW) and DHW priority (the larger of the two), with a bivalent-point analysis of candidate machines.
Results
- Heating: 2.51 kW peak (about 24 W/m²) and 5,743 kWh/yr, i.e. 55 kWh/m²·yr, under the 60 kWh/m²·yr target for the building.
- Hot water: a 174 L tank at 60 °C with a 5.08 kW coil covers a 332 L peak demand at 40 °C; 1,883 kWh/yr.
- Cooling: 3.28 kW building peak at 12:00. Room peaks do not coincide, so this is below the 3.43 kW sum of room peaks; sizing on the sum would oversize the plant.
- Radiant floor: one circuit per room; the warmest winter floor surface is 22.9 °C, well below the 29 °C comfort limit. The bathroom would fall below the dew point in cooling mode, so its loop is closed in summer or paired with dehumidification.
- Heat pump: DHW-priority sizing (5.61 kW) instead of additive sizing (8.47 kW) avoids a machine more than 3× oversized for the space-heating load. Selected unit: Vaillant aroTHERM plus VWL 55/6 A (R290, monobloc), with a 3-way valve giving hot water priority.